Vacuum Contactor Canja Fuse Haɗin Kayan Aiki
Yanayin yanayi
1) Yanayin zafin jiki: -25 ℃ ~ + 45 ℃, kullum matsakaita: ≤35 ℃
2) Tsayi: 1000m (Standard);iya har zuwa 4500m don oda na musamman;
3) Dangi zafi: matsakaita kullum ≤95%, kowane wata ≤90%;
4) Ƙarfin girgizar ƙasa ≤8 digiri;
5) Lokuttan da ake amfani da su ya kamata su kasance masu ƙin ƙonewa, fashewar abubuwa, lalata da girgiza mai tsanani.
Babban Ma'aunin Fasaha na Gpvc Vacuum Contactor-fuse Combination Apparatus
Abubuwa | Naúrar | Bayanai | |||
Ƙimar Wutar Lantarki | kV | 3.6 | 7.2 | 12 | |
Mitar wutar lantarki 1min jure irin ƙarfin lantarki | kV | 20 | 32 | 42 | |
Hasken haske yana jure wa wutar lantarki | kV | 46 | 60 | 75 | |
Ƙididdigar halin yanzu | A | 400 | 315 | 200 | |
Ƙididdigar ɗan gajeren lokaci jure halin yanzu (4s) | kA | 4 | |||
Ƙimar kololuwar jure halin yanzu | kA | 10 | |||
Tsammanin ɗan gajeren zango mai karya halin yanzu | kA | 50 | |||
Ana tsammanin gajeriyar kewayawa kusa da halin yanzu | kA | 130 | |||
Babban juriya na kewaye | ku | ≤250+ RF amfani | |||
Max.canja wurin halin yanzu | A | 4000 | 4000 | 3200 | |
An ƙididdige lokutan karyewar halin yanzu | sau | 250,000 | |||
Rayuwar injina | Nau'in riƙon inji | sau | 300,000 | ||
Nau'in riƙon lantarki | sau | 500,000 | |||
Babban juriya na kewaye | ku | ≤150 |
Shirin Haɗin Gpvc Vacuum Contactor-fuse
Lambar tsari | Tsari -1 | Tsari - 2 | |
Tsarin farko | |||
| Ƙididdigar halin yanzu (A) | ~400 | ~400 |
Babban aka gyara | Vacuum contactor-Fuse hade - GPVC | 1 | 1 |
Canjin canji na yanzu LZZBJ | 3 | 3 | |
Canjin wutar lantarki JDZ10 ko JDZX10 |
|
| |
Babban ƙarfin lantarki fuse XRNM-10 | 3 | 3 | |
Saukewa: GPJN15-12 |
| 1 | |
Na'urar lura da wutar lantarki | Kamar yadda buƙatun Masu amfani | Kamar yadda buƙatun Masu amfani | |
Jawabi | Tukin mota | Tukin mota |