GPN2S/GPN2E-40.5kV Nau'in Cubicle Gas Insulated Switchgear
Takaitawa
Nau'in Cubicle Gas Insulated Switchgear (CGIS) na cikin gida ne, masana'anta-harhada, ƙarfe-rufe, nau'in cubicle gas mai rufi switchgear don aikace-aikacen busbar guda ɗaya, gami da "Nau'in Green" GPN2E-40.5, GPN2N-40.5 da "Standard Type" GPN2S- 40.5.
"Nau'in Green" GPN2N-40.5 an ƙirƙira shi don amfani da nitrogen mai tsafta azaman iskar gas don samfuran samfuran tare da fasahar rufewar iskar gas ɗin da ba SF6 ba, wanda ya kawo ingantaccen kare muhallin kore na kayan maye gurbi.
"Nau'in Green" GPN2E-40.5 ya haɗa da fasaha na ci gaba na haɗakar da iskar gas (SF6 + N2) da masu fashewa, ƙyale kayan aiki suyi aiki a cikin mafi aminci da kuma yanayin muhalli.
The "Standard type" GPN2S-40.5 ne na 100% SF6 insulated, high yi da sauki amfani.
Tare da masana'antar dijital ta zamani da gwaji ta atomatik haɗe tare da firikwensin, saka idanu da fasahar kariya, CGIS ya dace da buƙatun rarraba wutar lantarki.CGIS ya dace musamman ga masana'antu tare da manyan buƙatun aminci kamar hanyoyin sadarwa na Wutar Lantarki, Ma'adinai, Sufuri na Rail, Shuke-shuken Petrochemical, Farms na iska da Tsarin Rail na Metropolitan.
Yanayin aiki na yau da kullun
An ƙirƙiri ainihin maɓalli don yanayin sabis na yau da kullun don sauyawa na cikin gida zuwa GB 3906, DL/T404 da IEC 62271-200.Ƙimar iyaka masu zuwa, da sauransu, ana amfani da su:
Yanayin yanayin yanayi
Matsakaicin zafin jiki: +45 ℃
Mafi ƙarancin iska: -25 ℃
Matsakaicin matsakaicin yau da kullun: +35 ℃
Danshi:
Matsakaicin ƙimar yau da kullun na yanayin zafi: ≤ 95%
Matsakaicin ƙimar dangi na kowane wata: ≤ 90%
Matsakaicin ƙimar yau da kullun na matsa lamba na ruwa: ≤ 2.2 × 10-3MPa
Matsakaicin ƙimar matsa lamba na ruwa na wata-wata: ≤ 1.8 × 10-3MPa
Tsayinsa: ≤ 1000m
Iskar da ke cikin yanayi ba ta ƙazantar da ƙura, hayaki ba,
iskar gas mai lalacewa da/ko mai ƙonewa, tururi ko gishiri.
Sharuɗɗan sabis na musamman
Hakanan ana iya amfani da samfurin don yawancin sharuɗɗan sabis na musamman.
Idan yanayin sabis ɗin ya wuce yanayin sabis na yau da kullun, waɗanda ba su da daidaitattun GB 11022 da IEC 62271-1, da fatan za a tuntuɓi GP a gaba don tabbatarwa:
Tsayin tsayi sama da 1000m.
Mafi girman yanayin muhalli.
Ƙananan zafin yanayi.
Wasu yanayi na musamman na muhalli.
Rage fitar da iskar gas
CGIS ya haɗa da ingantattun fasahohin Nitrogen mai tsabta ko gaurayen iskar gas (SF6 + N2) da masu hana ruwa gudu, zaɓi na asali da GP ya yi don taimakawa wajen rage tasirin greenhouse.SF6 (sulphur-hexafluoride) yana cikin jerin iskar gas mai zafi a cikin Yarjejeniyar Kyoto, tare da yuwuwar dumamar yanayi (GWP) na 23,000.Yawancin sauran matsakaicin tsarin wutan lantarki masu sauyawa suna amfani da iskar SF6 a matsayin matsakaicin insulating kawai.Zubar da iskar gas SF6 daga sauya kayan aiki yana ba da gudummawa ga barazanar tasirin greenhouse da canjin yanayi mai alaƙa.
Tare da jajircewarmu na kare muhalli, CGIS na taimakawa rage hayakin iskar gas ta hanyar amfani da gauraye da fasahar da aka haɗa da iskar gas tare da fasahar canza mata.
Ana samun raguwar 100% ko 50% a cikin SF6 ta amfani da Nitrogen (N2) gauraye masu fashewar iskar gas.Nitrogen shine mafi girman sashin iska kuma samfurin bazuwar sa ba mai guba bane.Haɗuwa tare da masu haɗin toshe-in da kuma yanayin yanayin ɓangarorin yana tabbatar da sauƙi na shigarwa da tsawo ba tare da buƙatar ƙarin ayyukan sarrafa iskar gas a kan shafin ba.
Amfani
●70% Rage A Girman Canji
Ingantacciyar ƙirar filin lantarki haɗe tare da kyakkyawan aikin rufewa, yana haifar da ƙaramin samfurin sauya kayan aiki wanda ke aiki cikin aminci da dogaro.
Ajiye 70% sarari idan aka kwatanta da maɓalli mai rufin iska.
Sake gyarawa cikin dakin sauya sheka abu ne mai sauki.
Rage farashin tashar tashar ƙasa.
●Mafi Girman Tsaro Don Mai aiki da Kayan aiki
Matsakaicin matsi na aiki na cubicle shine 0.00MPa (20 ℃).Wannan yana nufin, ko da a ƙarƙashin irin wannan yanayi mai tsanani, har yanzu yana kula da matakin da aka ƙididdige shi kuma yana kiyaye duk ayyukan da aka ƙididdige shi.Godiya ga ƙarancin iskar gas, ko da gas ɗin yana tserewa daga mashin ɗin, har yanzu cubicle na iya ci gaba da samun kuzari.An ƙera maƙullan wutar lantarki masu dogaro da injina tsakanin mai watsewar kewayawa da maɓalli uku don hana rashin aiki.
●Sauƙaƙan Shigarwa/Ƙarancin Aiki da Kuɗin Kulawa
Za'a iya cire bangarori a tsakiya cikin sauƙi don kiyayewa ba tare da motsi maƙwabta ba, ƙara yawan samuwa.
Ma'aunin Fasaha
Gabaɗaya | Naúrar | Daidaitaccen nau'in GPN2S-40.5 | Nau'in Kore GPN2E-40.5 | Nau'in Kore GPN2N-40.5 | |
Ƙarfin wutar lantarki | kV | 36/38/40.5 | 36/38/40.5 | 36/38/40.5 | |
Ƙididdigar mitar wutar lantarki jure irin ƙarfin lantarki (minti 1) | Zuwa duniya/lokaci zuwa lokaci | kV | 95 | 95 | 95 |
Ketare keɓewar nesa | kV | 118 | 118 | 118 | |
Zuwa duniya/lokaci zuwa lokaci | kV | 185 | 185 | 185 | |
Ketare keɓewar nesa | kV | 215 | 215 | 215 | |
Ƙididdigar mita | Hz | 50/60 | 50/60 | 50/60 | |
Ƙididdigar halin yanzu | A | 1250, 2500, 3150 | 1250, 2500 | 1250, 2500 | |
Single capacitor bank karya iya aiki | A | 400/400 | 400/400 | 400/400 | |
Ƙididdigar kebul na caji mai karye halin yanzu | A | 50 | 50 | 50 | |
An ƙididdige ɗan gajeren da'ira karya halin yanzu | kA | 20/25/31.5 | 20/25/31.5 | 31.5 | |
Ƙididdigar gajeren kewayawa yin halin yanzu (kololuwa) | kA | 50/63/80 | 50/63/80 | 80 | |
Ƙididdigar ɗan gajeren lokaci yana jure halin yanzu da lokacin juriya | ka/s | 20/3, 25/3, 31.5/3s | 20/3, 25/3, 31.5/3s | 31.5/3s | |
Ƙimar kololuwar jure halin yanzu | kA | 50/63/ 80 | 50/63/ 80 | 80 | |
Tsarin aiki | O-0.3s-CO-180s-CO | O-0.3s-CO-180s-CO | O-0.3s-CO-180s-CO | ||
Tsarin iskar gas mai rufi | 100% SF6 | 50% SF6+50% N2 | 100% N2 | ||
Yawan zubewar shekara | %/Y | ≤ 0.1 | ≤ 0.1 | ≤ 0.1 | |
Matsakaicin iskar gas (abs, 20˚C) | MPa | 0.12 | 0.12 | 0.12 | |
Matsin ƙararrawa (abs, 20˚C) | MPa | 0.11 | 0.11 | 0.11 | |
Matsakaicin aiki (abs, 20˚C) | MPa | 0.10 | 0.10 | 0.10 | |
Digiri na Kariya Tankin gas | IP65 | IP65 | IP65 | ||
Yadi | IP4X | IP4X | IP4X | ||
Motoci da na'urorin tafiya Mai jujjuyawa yana cajin motar | W | 90 | 90 | 90 | |
Ƙididdigar ƙarfin rufewa | W | 220 | 220 | 220 | |
Ƙarfin ƙima na buɗe wuta | W | 220 | 220 | 220 | |
Ƙididdigar ƙarfin lantarki na ƙarin kewaye | V | DC 24, 48, 110, 220;AC220 | DC 24, 48, 110, 220;AC220 | DC 24, 48, 110, 220;AC220 | |
Mitar wutar lantarki na 1 min yana jure wa ƙarfin lantarki na kewayen taimako | kV | 2 | 2 | 2 | |
Girma da Nauyi Girma (W×D×H)1250A | mm | 600×1600×2400 | 600×1500×2400 | 800×1700×2300 | |
Girma (W×D×H)2500A | mm | 800×1600×2400 | 800×1500×2400 | 900×1700×2300 | |
Nauyin 1250A | kg | 800 ~ 1000 | 800 ~ 1000 | 800 ~ 1000 | |
Nauyin 2500A | kg | 1100 ~ 1400 | 1100 ~ 1400 | 1100 ~ 1400 |
Tsarin daidaitaccen nau'in GPN2S-40.5 da nau'in kore GPN2E-40.5
Daidaitaccen nau'in GPN2S-40.5kV
Koren irin GPN2E-40.5kV
1. Sashin kariya da sarrafawa
2. Ƙananan ƙarfin lantarki
3. Tsarin VCB
4. Ƙwaƙwalwar igiya mai ƙura
5. Ƙofar ɗaki mara nauyi
6. Gas yawa nuna alama
7. Tankin gas na VCB
8. 3-matsayi canza tsarin
9. 3-matsayi
10. Babban busbar
11. Babban tankin busbar gas
12. murfin gaba
13. Wanda ya kamu da cutar
14. Na'urar rage matsi na babban tankin busbar gas
15. Ciki-mazugi na USB bushing
16. Cable m
17. igiyoyi
18. Rufin baya
19. Na'urar taimako na matsin lamba na tankin gas na VCB
20. CT
IST 3-matsayi inji
IST 3-madaidaicin matsayi
GPN2S VCB gas tank
Saukewa: GPN2S-40.5
Tsarin daidaitaccen nau'in GPN2S-40.5 da nau'in kore GPN2E-40.5Tsarin nau'in koren GPN2N (No-SF6)
Koren irin GPN2N-40.5kV
1. Naúrar kariya da sarrafawa
2. Ƙananan ƙarfin lantarki
3. Tsarin VCB
4. Ƙwaƙwalwar igiya mai ƙura
5. Ƙofar ɗaki mara nauyi
6. Gas yawa nuna alama
7. Tankin gas na VCB
8. 3-matsayi canza tsarin
9. 3-matsayi
10. Babban busbar
11. Babban tankin busbar gas
12. murfin gaba
13. Wanda ya kamu da cutar
14. Na'urar rage matsi na babban tankin busbar gas
15. Ciki-mazugi na USB bushing
16. Cable m
17. igiyoyi
18. Rufin baya
19. Na'urar taimako na matsin lamba na tankin gas na VCB
20. CT
21. Duniya mashaya
22. Wutar lantarki (na zaɓi)
An kafa na'ura mai ba da hanya tsakanin hanyoyin sadarwa, yayin da aka jera sandunansa masu kashi uku a tsaye a cikin tankin iskar gas.
Saboda fasahar sauya injin injin, an iyakance baka a cikin mai katsewa, yana rage yawan iskar gas mai rufewa.Maɓallin injin yana da babban aiki a cikin gajeriyar kewayawa akai-akai da aikace-aikacen sauya kaya masu yawa.