A'a. | Abubuwa | Naúrar | Bayanai | |||
1 | Ƙarfin wutar lantarki | kV | 40.5 | |||
2 | Ƙididdigar mita | Hz | 50 | |||
3 | Mitar wutar lantarki na 1min jure ƙarfin lantarki | Tsakanin sanduna, Zuwa ƙasa | kV | 95 | ||
Karaya | 118 | |||||
Wutar walƙiya jure ƙarfin lantarki | Tsakanin sanduna, Zuwa ƙasa | 185 | ||||
Karaya | 215 | |||||
4 | Ƙididdigar halin yanzu | A | 1250 1600 2000 2500 | |||
5 | Ƙididdigar ɗan gajeren lokaci jure halin yanzu (RMS) | kA | 25 | 31.5 | ||
6 | Ƙimar kololuwar jure halin yanzu | 63 | 80 | |||
7 | Rated short-circuit breaking current (RMS) | 25 | 31.5 | |||
8 | Ƙimar gajeriyar kewayawa na yanzu (ƙimar kololuwa) | 63 | 80 | |||
9 | An ƙididdige ɗan gajeren lokacin da'ira | s | 4 | |||
10 | Matsakaicin jerin ayyuka | O-0.3s-CO-180s-CO | ||||
11 | Ƙididdigar ɓoyayyiyar ɓarnar ɓarnar da ba ta cikin lokaci ba | kA | 21.7 | 27.4 | ||
12 | Ƙididdigar kebul na cajin gwajin sauyawa na yanzu | A | 50 | |||
13 | rated guda/baya-baya capacitor bank breaking current | 800/800 | ||||
14 | Rayuwar injina | sau | 10000 | |||
15 | Gajeren lokacin da'ira na yanzu | sau | 30 | |||
16 | Da'irar ta biyu 1 min mitar wuta tana jure irin ƙarfin lantarki | 2000 | ||||
17 | Ƙimar wutar lantarki mai aiki | Rufe coil | V | DC110/220, AC220 | ||
Bude coil | V | DC110/220, AC220 | ||||
18 | Ƙididdigar ƙarfin lantarki na injin ajiyar makamashi | W | DC110/220, AC220 | |||
19 | Ƙarfin ƙima na injin ajiyar makamashi | s | 250 | |||
20 | Lokacin ajiyar makamashi (ƙimar ƙarfin lantarki) | s | ≤10 | |||
21 | Matsakaicin ƙimar gas na SF6 (matsa lamba a 20 ° C) | Mpa | 0.350+0.02 | |||
22 | Matsin ƙararrawa | Mpa | 0.29± 0.01 | |||
23 | Mafi ƙarancin matsi na aiki (matsi na toshewa) | Mpa | 0.28± 0.01 | |||
24 | Adadin zubewar shekara | % | ≤0.5 | |||
25 | Gas abun ciki na danshi | μL/L | ≤150 | |||
26 | Motsawa bugun lamba | mm | ≥78 | |||
27 | Tazarar lamba | mm | 50± 1.5 | |||
28 | Lokacin budewa | ms | 60-78 | |||
29 | Lokacin rufewa | ms | 65-95 | |||
30 | Rufewa da buɗewa sau uku ba na lokaci-lokaci ba ne | ≤5 | ||||
31 | Matsakaicin saurin buɗewa (a cikin 10ms bayan rabi) | ms | 2.2 ~ 2.8 | |||
32 | Matsakaicin saurin rufewa (a cikin 10ms bayan rabin hanya) | ms | ≥1.5 | |||
33 | Babban juriya na madauki | μΩ | ≤32 (Kwayoyin hannu) | ≤20 (Kafaffen nau'in) |