GPN1-12kV Mai Cire AC Ƙarfe Mai Rufaffen Sauyawa
Yanayin yanayi
Yanayin yanayi: -25 ℃ ~ + 45 ℃, kullum matsakaita: ≤35 ℃
Tsayinsa: 1000m( Standard);iya har zuwa 4500m don oda na musamman;
Dangantakar zafi: matsakaita kullum ≤95%, matsakaicin kowane wata ≤90%;
Ƙarfin girgizar ƙasa ≤8 digiri;
Abubuwan da ake amfani da su ya kamata su kasance masu kuɓuta daga abubuwan ƙonewa, fashewar abubuwa, lalata da girgiza mai tsanani.
Samfura
Siffar samfuran
1) Wannan samfurin yana aiki don namu GPVN-12kV / 17Kv / 24kV sakawa ko insulating injin injin kewayawa ko ABB's VD4 vacuum circuit breaker.
2) Our samar sanyi GPVC injin contactor - fiusi hade ko ABB kamfanin ta VC injin contactors, wanda za a iya hada da FC madauki cubicle, saduwa da wutar lantarki tsarin da wutar lantarki da kuma bukatar sauran masana'antu da kuma ma'adinai Enterprises.
3) Yin amfani da kyakkyawan aluminum-zinc clad karfe farantin ta daidai CNC machining kayan aiki a cikin majalisar ministocin, da kuma yin amfani da biyu lankwasawa tsari, ƙwarai inganta ƙarfi na majalisar.
4) Door surface ta epoxy guduro electrostatic foda fesa tsari, juriya na lalata, hadawan abu da iskar shaka, tasiri da kuma karfi adhesion.
5) Ginin majalisar da aka rufe yana da cikakken tsari, an raba sassan aikin gaba daya.Lokacin da aka rufe kofa, zai iya cimma aikin na'ura mai wanki da ƙasa.
6) Daidaitaccen dunƙule drive inji, tabbatar da trolley da mai kyau interchangeability.
7) Cikakken tsari na farko don biyan buƙatun masu amfani daban-daban, kuma yana ba da damar shirin trolley biyu.
8) Saurin saukar da ƙasa mai sauri don yin ƙasa da gajeriyar kewayawa, da kuma cimma aikin lantarki (Motorized).
9) Hanya mai sauƙi kuma mai tasiri "Tsarin Tsaro Biyar" na iya dogara da hana amfani da rashin amfani da tabbatar da amincin mai aiki.
10) Switchgear na nau'in proof ne na Arc, a saman rukunin bas, rukunin ɓangarorin Vacuum, da rukunin tashar tashar USB suna sanye da na'urorin taimako na matsa lamba.
11) Bangaren kebul yana da wadataccen sarari, ana iya haɗa shi cikin sauƙi zuwa yawancin igiyoyi, kuma tabbatar da tsayin shigarwa na filogin na USB.
12) Ƙimar kariya ta ƙaƙƙarfan (IP4X), don hana ƙaƙƙarfan ƙwayoyin waje ko mamayewar kwaro.
13) Tsarin sakandare na zaɓin bin na'urar saka idanu na tsaro yana da aikin tantance kansa da sadarwa na bayanai, kwamfuta mai haɗaɗɗiyar fasaha, don cimma nasarar sarrafa nesa, telemetry mai nisa, kallon nesa, daidaitawa ta nesa.
14) Haɗu da GB3906, GB / T11022, DL404 da IEC60298, IEC62271-1 ma'auni, kuma ta hanyar cikakken gwajin nau'in gwaji da gwajin plateau (3000m).
15) An ƙetare gwaje-gwajen dacewa na lantarki a cikin babban dakin gwaje-gwajen gwajin kayan aikin wuta.
A.Tsarin fasaha Don 12Kv switchgear
Abu | Naúrar | Bayanai | |
Ƙarfin wutar lantarki | kV | 6 ~ 12 | |
Ƙididdigar mita | Hz | 50/60 | |
Ƙididdigar halin yanzu | A | 630-4000 | |
Matsayin rufewa | Mitar wutar lantarki 1min (Phase to earth / fadin bude lambobin sadarwa) | kV | 42/48 |
Wutar walƙiya tana jure wa wutar lantarki (Mataki zuwa ƙasa/faɗin buɗe lambobin sadarwa) | kV | 75/85 | |
Babban motar bus ɗin da aka kimanta halin yanzu | A | 1250,1600,2000,2500,4000 | |
Sub-busbar rated halin yanzu | A | 630,1250,1600,2000,2500,3150 | |
Ƙididdigar ɗan gajeren lokaci jure halin yanzu(4s) | kA | 16,20,25,31.5,40,50 | |
Ƙimar kololuwar jure halin yanzu | kA | 40,50,63,80,100,125 | |
Digiri na kariya | Ƙofar IP4X, IP2X (An buɗe ƙofar VCB) | ||
Girman fayyace (nisa/zurfin/tsawo) | mm | 650(800,1000) /1500(1300,1670,2000) /2300 | |
Nauyi | kg | 500-1200 |
Tsarin zane na cubicle 630A ~ 1250A
Tsarin zane na cubicle 1600A ~ 4000A
Teburin sigogi na fasaha na B.Main don 17.5kV switchgear
A'a. | Suna | Naúrar | Bayanai | |
1 | Ƙarfin wutar lantarki | kV | 15/17.5 | |
2 | Matsayin rufewa | 1 min mitar ƙarfin juriya irin ƙarfin lantarki (RMS) | kV | 50 |
Ƙunƙarar ƙwanƙwasa mai jurewa ƙarfin lantarki (kololuwar) | 95 | |||
3 | Ƙididdigar halin yanzu | A | 630-4000 | |
4 | An ƙididdige ɗan gajeren kewayawa buɗe halin yanzu | kA | 50 | |
5 | Ƙididdigar mitar wutar lantarki | Hz | 50/60 | |
6 | Ƙimar gajeriyar kewayawa na yanzu (kololuwa) | kA | 130 | |
7 | Ƙimar kololuwar jure halin yanzu | kA | 130 | |
8 | Ƙididdigar ɗan gajeren lokaci jure halin yanzu | kA | 50 | |
9 | Rayuwar lantarki | sau | 20 | |
10 | An ƙididdige ɗan gajeren lokaci na halin yanzu | s | 4 | |
11 | Rayuwar injiniyoyi na VCB | sau | 10000 | |
12 | Matsayin kariya na cubicle | Ƙofar IP4X, IP2X (An buɗe ƙofar VCB) | ||
13 | Girman fa'ida (W*D*H) | mm | 800/1000*1500/1670*2300 | |
14 | Nauyi | kg | 500-1200 |
C.Technical ƙayyadaddun don 24kV switchgear
Abu | Naúrar | Bayanai | |
Ƙarfin wutar lantarki | kV | 24 | |
Ƙididdigar mita | Hz | 50/60 | |
Ƙididdigar halin yanzu | A | 630,1250, 1600, 2500, 3150, 4000 | |
Matsayin rufewa | Mitar wutar lantarki 1min (phase to earth / fadin bude lambobin sadarwa) | kV |
65 |
Wutar walƙiya tana jure wa wutar lantarki (phase to earth / fadin bude lambobin sadarwa) | kV |
125 | |
Ƙididdigar ɗan gajeren lokaci jure halin yanzu(4s) | kA | 20, 25, 31.5 | |
Ƙimar kololuwar jure halin yanzu | kA | 50, 63, 80 | |
Digiri na kariya | Yadi: IP4X, bude kofa: IP2X | ||
Girman fayyace (nisa x zurfin x tsayi) | mm | 1000(800)x1820(1500)x2430(2300) | |
Nauyi | kg | 1200-1500 |
1. Za a yi la'akari da ƙananan ƙarfin kewayawa na CT daban;
2. Jadawalin layin da ke fita a baya ya kamata ya sami ƙarin takubile.